Overview
ZAZQ(X) electric three-way control valve is available in converging and diverging types. It consists of a DKZ electric actuator and a three-way converging or diverging valve body. Driven by electric power, it accepts the unified standard signal of 0-10 mA DC or 4-20 mA DC, and the valve opening corresponds to the operating signal. The converging valve merges two fluid streams into one, while the diverging valve splits one fluid stream into two. The converging and diverging valves can only be selected correspondingly; however, when DN ≤ 80, the converging valve can be used for diverging applications. It can replace two single-seat or double-seat control valves, saving investment and occupying less space. Three-way control valves are commonly used for regulating two media in heat exchangers and for simple ratio control.
Control Valve Technical Parameters
|
Nominal Diameter (mm)
|
Converging
|
25
|
32
|
40
|
50
|
65
|
80
|
100
|
125
|
150
|
200
|
250
|
300
|
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Diverging | 80 | 100 | 125 | 150 | 200 | 250 | 300 | ||||||
| Rated Flow Coefficient Kv | Converging | 8.5 | 13 | 21 | 34 | 52 | 85 | 135 | 210 | 340 | 535 | 800 | 1260 |
| Diverging | 85 | 135 | 210 | 340 | 535 | 800 | 1260 | ||||||
| Nominal Pressure (MPa) | 1.6, 4.0, 6.4 | ||||||||||||
| Flow Characteristic | Linear | ||||||||||||
| Actuator | Type II | DKZ-310 | DKZ-310 | DKZ-410 | DKZ-510 | DKZ-510 | |||||||
| Type III | DKZ-310C | DKZ-310C | DKZ-410C | DKZ-510C | DKZ-510C | ||||||||
| Output Thrust (N) | 4000 | 4000 | 6400 | 16000 | 16000 | ||||||||
| Stroke (mm) | 16 | 25 | 40 | 60 | 100 | ||||||||
| Bonnet Type | Plain (normal temperature), cooling-fin (medium temperature) | ||||||||||||
| Allowable Differential Pressure (MPa) | 1.6 | 1.0 | 2.5 | 1.6 | 1.5 | 1.0 | 0.65 | 0.4 | 0.3 | 0.16 | 0.26 | 0.18 | |
| Working Temperature (°C) | -40 ~ 230 °C (normal temperature type); 230 ~ 450 °C with cooling-fin bonnet (medium temperature type); -100 ~ 600 °C (special order) | ||||||||||||
| Rangeability | 30:1 | ||||||||||||
| Flange Standard | Cast iron per JB78-59; cast steel per JB79-59 | ||||||||||||
| Input Impedance | Type II: 200; Type III: 250 | ||||||||||||
| Factory Setting | Direct-acting as standard (with respect to the upper seat); if reverse-acting is required, please specify when ordering. | ||||||||||||
Performance Specifications
|
Item
|
Value
|
|
|---|---|---|
| Basic Error (%) | ≤±3.5 | |
| Hysteresis (%) | ≤2.5 | |
| Dead Band (%) | ≤3.0 | |
| Start/End Point Deviation (%) | Direct-acting, reverse-acting | ±2.5 |
| ±2.5 | ||
| Allowable Leakage (L/h) | Class III per JB/T7387-94, less than rated valve capacity ×10-3 | |
Overall Dimensions
|
Nominal Diameter DN
|
A
|
L
|
H
|
H1
|
|||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Diverging
|
Converging
|
PN1.6
|
PN4.0
|
PN6.4
|
Diverging
|
Converging
|
PN1.6
|
PN4.0
|
PN6.4
|
PN1.6
|
PN4.0
|
PN6.4
|
|||
|
Plain
|
Cooling-fin
|
Plain
|
Cooling-fin
|
||||||||||||
| 25 | 520 | 490 | 185 | 190 | 200 | 715 | 865 | 140 | 150 | 160 | |||||
| 32 | 520 | 490 | 200 | 210 | 210 | 721 | 871 | 150 | 160 | 170 | |||||
| 40 | 520 | 490 | 220 | 230 | 235 | 733 | 883 | 160 | 170 | 180 | |||||
| 50 | 520 | 490 | 250 | 255 | 265 | 748 | 898 | 180 | 190 | 200 | |||||
| 65 | 520 | 520 | 275 | 285 | 295 | 839 | 999 | 200 | 220 | 220 | |||||
| 80 | 520 | 520 | 305 | 310 | 320 | 872 | 1032 | 842 | 1002 | 225 | 250 | 265 | 210 | 230 | 240 |
| 100 | 520 | 520 | 350 | 355 | 370 | 896 | 1056 | 846 | 1006 | 245 | 275 | 285 | 220 | 250 | 260 |
| 125 | 520 | 520 | 410 | 425 | 440 | 947 | 1162 | 897 | 1112 | 284 | 320 | 325 | 260 | 300 | 300 |
| 150 | 520 | 520 | 450 | 460 | 475 | 947 | 1162 | 897 | 1112 | 305 | 340 | 340 | 280 | 320 | 320 |
| 200 | 520 | 520 | 550 | 560 | 570 | 965 | 1180 | 905 | 1120 | 350 | 400 | 410 | 320 | 380 | 380 |
| 250 | 520 | 520 | 670 | 740 | 750 | ||||||||||